8
Average Results of Analyses of Metropolitan Water Board
Supply. (Milligrammes per litre). Water filtered and
chlorinated at Hampton Works.

Chemical

Ammonia Nitrogen0.020
Albuminoid Nitrogen0.076
Oxidised Nitrogen (Nitrate)3.9
Chlorides as C129
Oxygen abs. from Permanganate 4 hours at 27°C.1.20
Turbidity in terms of Silica0.4
Colour m.m. brown 2 ft. tube Burgess's Tintometer12
Hardness total260
Hardness (Non-carbonate)58
pH Value7.9
Conductivity550

Bacteriological
Plate counts (average per ml.)
Colonies counted on agar at 37°C. (20—24 hours) 3.7
Colonies counted on agar at 22°C. (3 days) —
Coliform Test (Percentage of samples negative per 100 ml.)
Coliform 99.50
B.Coli 99.75
Typical Analysis of South West S.W. Co., Supply
(Parts per million.)
Chemical
Appearance Bright with
very few
particles.
(Microscopic
mineral
particles)
Turbidity Less than 3
Colour 5
Odour Nil
pH 7.7
Free Carbon Dioxide 7
Electric Conductivity 510
Total Solids 340
Chlorine present as Chloride 28
Alkalinity as Calcium Carbonate 195
Hardness: Total 255
(Carbonate 195; Non-Carbonate 60)
Nitrate Nitrogen 4.7
Nitrite Nitrogen absent
Ammoniacal Nitrogen 0.000
Albuminoid Nitrogen 0.044
Oxygen absorbed 0.80
Residual Chlorine 0.08
Metals absent