London's Pulse: Medical Officer of Health reports 1848-1972

View report page

Wembley 1936

[Report of the Medical Officer of Health for Wembley]

This page requires JavaScript

CHEMICAL AND BACTERIOLOGICAL WATER

REPORTS.

CHEMICAL.Sample of Water. Colne Valley Water Co. 20/7/36.Sample of Water. L.M.S. Railway Supply. 16/12/36.Sample of Water. Rickmansworth & Uxbridge Public Supply. 12/8/36.
Parts per 100,000Grains per Gallon.Parts per 100,000Grains per Gallon.Parts per 100,000Grains per Gallon.
Total Solids (dried at 120°C)39.0027.3017.011.936.525.6
Combined chlorine7.805.462.501.757.505.25
equivalent to Na CI12.879.014.132.8912.388.67
Nitric nitrogen (Nitrates)0.500.350.460.320.500.35
Nitrous nitrogen (Nitrites)NilNilNilNilNilNil
Ammoniacal nitrogen0.00020.00010.00100.00070.00030.0002
Albuminoid nitrogen0.00360.00250.00700.00490.00280.0020
Oxygen absorbed in 4 hours at 27°C0.0350.0240.0710.0500.0310.022
Lead or CopperNilNilNilNilNilNil
Temporary hardness (equivalent to CaCo3)15.010.53.52.416.011.2
Permanent hardnessNilNil4.53.2NilNil
Total hardness15.010.58.05.616.011.2
BACTERIOLOGICAL.
Average number of organisms producing visible colonies on gelatine plates, incubated at 200220C. for 3 days24 per c.c.44 colonies per c.c.7 per c.c.
Average number of organisms producing visible colonies on agar plates, incubated at 37.5°C. for 2 days10 per c.c.17 colonies per c.c.3 per c.c.
B. ColiNot found in 100 c.c.Not found in 100 c.c.Not found in 100 c.c.
StreptococciNot found in 30 c.c.Not found in 30 c.c.Not found in 30 c.c.
B. Welchii (spores)Not found in 100 c.c.Not found in 100 c.c.Not found in 100 c.c.
BACTERIOLOGIST'S REMARKS:Results shew this water to be quite satisfactory for drinking purposes.Results shew this water to be quite satisfactory for drinking purposes.Results shew this water to be quite satisfactory for drinking purposes.