Hints from the Health Department. Leaflet from the archive of the Society of Medical Officers of Health. Credit: Wellcome Collection, London
[Report of the Medical Officer of Health for Kingston-upon-Thames]
This page requires JavaScript
94
WATER SUPPLY
The following information has been kindly supplied by the
Director of Water Examination, Metropolitan Water Board.
All the water supplied to the Borough is derived from the
River Thames.
Yearly Average Bacteriological Results
Before Treatment
Number of Samples 8,087
Agar plate count per ml. 20-24 hours at 37°C 42.3
Coliform count -
Per cent. samples negative in 100 ml 41.94
Count per 100 ml 10.2
Escherichia coli count -
Per cent. samples negative in 100 ml 56.76
Count per 100 ml 4.0
After Treatment
Number of Samples 3,891
Agar plate count per ml. 20-24 hours at 37°C 10.0
Coliform count - per cent samples negative in 100 ml 99.85
E.coli count - per cent samples negative in 100 ml 99.97