(60)

LONDON UNDERGROUND WATER. Result at the Water Analysis at Private Wells in Chalk in the Metropolitan Borough of Bermondsey.

WELLDepth of well in feetGallons per hourPurpose for which water is usedApprox distance from ThamesPoint at which sample was takenCHEMICAL ANALYSIS. Parts per 100,000BACTERIOLOGICAL EXAMINATION
Combined ChlorineEquivalent to Sodium ChlorideFree AmmoniaAlbuminoid AmmoniaNitrogen as NitratesNitrogen as NitritesOxygen absorbed from Permanganate (3 hrs. at 37°C.)AppearanceNo. of microorganisms per cubic centimetre living and capable of development upon agar at 22°C.No. of microorganisms per cubic centimetre living and capable of development upon agar at 37°C.Microbes of Indication
Coliform GroupStreptococciCI. welchii
NO. 14009,000Solely for process½ mileFrom a hose connected to the pump19.5332.220.00970.00800.80Nil0.100Clear and Bright00Absent from 100 c.c.Absent from 100 c.c.Absent from 100 c.c.
NO. 24003,500Solely for process½ mileFrom a tap connected to the pump15.2725.200.09320.01020.25trace0.120slightly cloudy owing to suspended chalk4 moulds0Absent from 100 c.c.Absent from 100 c.c.Absent from 100 c.c.
NO. 34003,000Solely for process½ mileFrom supply to gelatine cooling trays15.5525.660.01750.00830.12trace0.19chalk Clear and Bright00Absent from 100 c.c.Absent from 100 c.c.Absent from 100 c.c.
NO. 43602,000Solely for process½ mileTaken from tap in yard16.0826.530.19430.00870.02Nil0.14Slight cloudiness due to chalk5 plus three moulds6 plus four moulds170 per 100 c.c. These are of the intermediate type II and are considered to beAbsent from 100 c.c.Absent from 100 c.c.
NO. 52507,000 10,000 (24 hrs.)Solely for process200 yds. (Docks)Taken from hose over water softener60.099.00.08160.00600.04slight trace0.112Slightly cloudy02of soil origin Probable number=25 Intermediate Type II. present in 100 c.c.Absent from 100 c.c.Present in 10 c.c.
NO. 62001,250Solely for process60 feetTaken from by-pass to boilers58.2296.060.02520.00920.1trace0.128Slightly cloudy and a deposit of rust608648Probable number=350 Intermediate Type I present in 100 c.c. in association with Ps. pyocyaneusAbsent from 100 c.c.Present in 10 c.c.
NO. 72403,000Cooling purposes only¾ mileTaken from tap in engine room on rising main3.365.540.01190.00830.33Nil0.082Clear and Bright01 air borne— contaminantAbsent from 100 c.c.Absent from 100 c.c.Absent from 100 c.c.
NO. 84252,000Solely for process100 yds. (Dock)Taken from pipe on top of pump in yard20.1433.230.12140.0068NilNil0.042Faintly cloudy00Absent from 100 c.c.Absent from 100 c.c.Absent from 100 c.c.
NO. 9200–Only used in an emergency½ mileTaken from hose connected directly on Electric Pump17.0028.050.14570.01110.04Nil0.080Cloudy and definitely yellow, due to iron11Absent from 100 c.c.Absent from 100 c.c.Absent from 100 c.c.